Data Sheet for Product
4
Siemens A6V11664139_en--_i
Smart Infrastructure 2022-01-13
Installation
Power is connected to a plug-in screw terminal block.
This connection is not required for Power over Ethernet (PoE).
Commissioning
Touch panels can be commissioned without tools.
All necessary network parameters can be entered directly on the unit.
Each device has a unique identification number to ensure efficient commissioning.
It is also printed on the removable barcode label.
LED display (front side)
Color Activity Function
Green Off Device is not powered
Flashing Start-up or the program is stopped
On Device is operational
Red Off OK
On Program error
Hardware fault
Flashing 1 Hz Wrong or corrupt software
No application loaded
Faulty server-link configuration
Flashes in wink command rhythm Physical device ID
Service button (rear side) (Only for devices with series B and higher, see printing on the device)
Press Description
Short Physical identification on the network (Ethernet)
As per
description
Do the following to reset the device to factory state:
1. Power off the device.
2. Power on the device.
3. Wait until the green LED lights up and turns off again, then press the Service button.
4. Keep the Service button pressed until the green LED lights up, then release the button.
5. Wait until the device has fully started – unconfigured (LED flashes red/green)
Pre-loaded apps are still available. The FW remains unchanged
Maintenance
Cleaning
Touch panels are maintenance free.
Dirt on the display can be cleaned using off-the-shelf display cleaners for smart phones, a
moist rag, and/or off-the-shelf microfiber cloth for monitors or glasses.
Recommended products:
● Lysol towel
● Clorex towel
● Water with 2% alcohol
● Damp microfiber cloth
● H
2
O
2
hydrogen peroxide
● Sterillium® Classic Pure
Firmware upgrade
You can update the firmware with ABT Site.
Repair
The devices cannot be repaired. The entire unit must be replaced.