Technical data
General device data
Operating voltage for 2
-pin connector
AC 24 V ± 20 % or
DC min. 12 V ... max. 40 V
Operating voltage when plugged into
modular automation station
AC 24 V ± 20
%, derived automatically
from modular automation station
E
lectrical voltage via Ethernet connection
Power Over Ethernet (POE)
to IEEE 802.3af
Safety extra low voltage SELV
Protective extra low voltage PELV
HD 384
Frequency
50/60 Hz
Power consumption
Series B and later
Series A
AC 24 V
max. 7 VA
max. 12 VA
DC 12
max. 3.5 W
max. 5 W
Internal fuse
Thermal, self-resetting
Operating data
Main processor
Freescale PowerPC
Data backup in case of power failure
Applications, parameter (FLASH)
> 10 years
Keyboard
Type
Keyboard with plastic mem
brane and
pressure point
Key area
7 x 7 mm
Switching pressure
2.1 N
Travel
0.6 ... 0.7 mm
Operating life
> 1 million operations
Material, front membrane
Polycarbonate
Material, contacts
Conductive silver,
snap-on discs gold-plated
Display
Mechanical
LCD display
F-STN, Black & White
Display area
123 x 68 mm
No. of dots
240 x 128 dots
Dot size
0.47 x 0.47 mm
Dot area
0.50 x 0.50 mm
Optical
Contrast ratio
20: 1
Viewing angle
± 40°
Viewing direction
6 o'clock
Background lighting
Series B and later
Series A
Type
LED
CCFL Cold Cathode Fluorescent Lamp
Brightness
150 cd/m
2
60 cd/m
2
Rise time lamp
0 s
5 min = 80% Brightness
Life span Lamp
50'000
hrs.
= 50 % Brightness
20'000 hrs. = 64 % Brightness