Data Sheet for Product
6
Siemens A6V12304192_en--_b
Smart Infrastructure 2021-07-16
Technical data
Power supply
Operating voltage 24 V AC (24 V≃, ⏊, ) AC 24V -15 / +20% (PELV)
AC 24V Class 2 (US)
48…63 Hz
Operating voltage 24V DC DC 24 V -15 / +20 % (PELV)
DC 24V Class 2 (US)
Functional ground(US)
Functional earth
The terminal for the functional ground must be
connected on the installation side with the building
grounding system (PE).
Screw terminals for wire cross sections up to Max. 2.5 mm
2
(14 AWG)
Internal fusing 2.5 A irreversible / non-replaceable
External supply line fusing (EU) Non-renewable fuse max. 10A slow
or
circuit breaker max. 13A
Tripping characteristic B, C, D per EN 60898
or
Power supply with current limitation of max. 10A
Power consumption (for transformer planning)
Power consumption AC
Base load
With USB (not supported)
10VA
16VA
Power consumption DC
Base load
With USB (not supported)
5W
8W
Function data
Hardware information
Processor NXP i.MX8 DualX, 1GHz
Storage 2 GB RAM
8 GB eMMC
Real-time clock
Energy reserve (Supercap) to support real-time clock (7 days).
Interfaces
Ethernet interface
Plug 2 x RJ45, shielded
Interface type 10Base-T / 100Base-TX, IEEE 802.3 compatible
Bit rate 10/100Mbps, autosensing
Protocol BACnet on UDP/IP and HTTPs on TCP/IP
Cabling, cable type 10Mbps: Min. CAT3, shielded cable is recommended
100Mbps: Min. CAT5, shielded cable is recommended
Cable length Max. 100m (330ft)
Screw terminals, plug-in
Cu-wire or Cu-strand with wire end sleeve 1 x 0.6mm ∅ to 2.5mm
2
(22 to 14AWG)
or 2 x 0.6mm ∅ to 1.0mm
2
(22 to 18AWG)
Cu-strand without wire end sleeve 1 x 0.6mm ∅ to 2.5mm
2
(22 to 14AWG)
or 2 x 0.6mm ∅ to 1.5mm
2
(22 to 16AWG)
Stripping length 6...7.5mm (0.24...0.29 in)