Data Sheet for Product

5
Siemens A6V12304192_en--_b
Smart Infrastructure 2021-07-16
Notes
Safety
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage.
Observe national provisions and comply with the appropriate safety regulations.
Mounting position and ambient temperature
The devices can be snapped onto standard rails or screwed onto a flat surface.
Plug-in screw terminals connect power and interfaces (except for Ethernet).
Ambient temperature -5...50°C (23...122°F) Ambient temperature -5...45°C (23...113°F)
Wall, horizontal
From left to right
From right to left
Overhead
Wall, vertically
From top to bottom
From bottom to top
On a horizontal surface
CAUTION
Risk of overheating for failure to comply with ambient temperature
Burning and damage to the device
Ensure sufficient ventilation to comply with the permissible ambient temperature within
the panel or installation box. The temperature must be at least 10K (18° F) lower out-
side the installation box.
Installation
WARNING
Electric shock
Incorrect installation of the device may lead to electric shock injuries when touching the
device!
Install the device in a lockable cabinet or use terminal covers.
Do not install the device in locations where children are likely to be present.
Conductors with a cross-section of 0.5 mm2 (AWG24) or greater shall comply with the
requirements of IEC 60332-1-2 and IEC 60332-1-3 or IEC TS 60695-11-21.
Disposal
The device is considered an electronic device for disposal in accordance
with the European Guidelines and may not be disposed of as domestic
garbage.
Dispose of the device through channels provided for this purpose.