Data Sheet for Product
4
Siemens A6V12304192_en--_b
Smart Infrastructure 2021-07-16
LED indicators and service pin
Activity LED / Interface Color Activity Function
Ethernet 1...2 Green Continuously ON
Continuously OFF
Flashing
Link active
No connection
Network traffic
Yellow Continuously ON
Continuously OFF
Link 100 Mbps
Link 10 Mbps
RUN Green Continuously ON
Continuously OFF
Flashing
Device operational
Device not operational
Start-up or program halted
Red Continuously OFF
Continuously ON
Rapid flashing
OK
HW or SW fault - power off and on the
device
Firmware or application missing/corrupted
Blue Continuously OFF Function not supported
SVC Red Continuously OFF
Flashing
OK
Device is not configured
Flashing per wink
command
Identification of the device after receipt of
wink command
2s
1s
5 Hz 5 Hz
2s
1s
COM1 / 2TX Yellow Continuously OFF Function not supported
COM1 / 2RX Yellow
Service button Short press Identification on the network
As per description: Do the following to reset the device to
factory state:
1. Power off the device.
2. Power on the device.
3. Wait until all LEDs light up and turn off
again, then press the Service button.
4. Keep the Service button pressed until
all LEDs light up, then release the but-
ton.
All LEDs turn off, the device restarts.
5. Wait until the device has fully started up
– unconfigured (green RUN LED and
red SVC LED are flashing).