User Manual
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Plant view
- 4 Alarms
- 5 Scheduler
- 6 List view
- 7 Trends
- 8 Reports
- 9 Documents
- 10 General settings
- Index
Plant view
Commanding objects
3
A6V11211557_en
--_g
21 | 64
② Commanding to Auto / Manual
The Auto / Manual toggle button displays for objects with a BACnet priority array.
● If commanded to Auto, the slot in the object’s priority array is cleared.
● If commanded to Manual, the object is commanded to the priority that has been assigned to the user role.
● If the toggle button is unavailable, check the integration status of the device and perform an integration, if
needed.
③ Changing the value
Some objects must be placed out-of-service before the value is changed. In this case, select Out of Service (①
in the figure) and then change the value.
● If minimum and maximum values have been defined for Analog objects, this range displays above the value
field.
● If the object has an Auto / Manual toggle button, it is placed into Manual control.
● If the object has a priority array, it is commanded to the priority that has been assigned to the user role.
④ Command action buttons
● Apply saves your changes and keeps the dialog box open for further commands.
● OK saves your changes and closes the dialog box.