User Manual

Table Of Contents
3
A6V11211557_en
--_g
21 | 64
② Commanding to Auto / Manual
The Auto / Manual toggle button displays for objects with a BACnet priority array.
If commanded to Auto, the slot in the object’s priority array is cleared.
If commanded to Manual, the object is commanded to the priority that has been assigned to the user role.
If the toggle button is unavailable, check the integration status of the device and perform an integration, if
needed.
③ Changing the value
Some objects must be placed out-of-service before the value is changed. In this case, select Out of Service (①
in the figure) and then change the value.
If minimum and maximum values have been defined for Analog objects, this range displays above the value
field.
If the object has an Auto / Manual toggle button, it is placed into Manual control.
If the object has a priority array, it is commanded to the priority that has been assigned to the user role.
④ Command action buttons
Apply saves your changes and keeps the dialog box open for further commands.
OK saves your changes and closes the dialog box.
Cancel closes the dialog box without applying any changes.