User Manual
Table Of Contents
- 1 About this document
- 2 Commissioning
- 2.1 Default connection
- 2.2 Initial login
- 2.3 Setup wizard
- 2.4 Discover and assign devices
- 2.5 Subscribing to the time master
- 2.6 Time synchronization of the time master
- 2.7 Registering as a foreign device
- 2.8 Touch panel settings
- 2.9 Operating and monitoring features
- 3 Data point integration
- 4 Graphic features
- 4.1 Plant view Tools
- 4.2 Kiosk graphics
- 4.3 Engineering notations
- 5 Graphics Builder
- 5.1 Overview
- 5.2 Pane tools
- 5.3 Graphics libraries
- 6 Graphics engineering
- 6.1 Using supersample graphics
- 6.2 Optimizing graphics for PXM touch panels and standard devices
- 6.3 Thumbnails
- 6.4 Dashboards
- 7 Advanced functionality
- 8 Tips and tricks
- 8.1 Updates required after a time zone change
- 8.2 APPLY BATCH TAGS
- 8.3 Graphic components within models cannot be modified
- 8.4 A graphic with relative binding that includes data points from different branches of the hierarchy cannot be created at the Root level
- 8.5 Relative hyperlinks cannot be added to a graphic at the Root level
- 8.6 Relative hyperlinks in a graphic are broken if the graphic is engineered offline and then imported to another device
- 8.7 Automatic logout from Desigo Control Point causes Graphics Builder to temporarily stop working
- 8.8 Detection of network interruptions
- 8.9 Cancelling a kiosk log out sequence
- 8.10 Special characters do not display in graphic file names
- 8.11 The color of a graphical component may display incorrectly if the component was copied
- Index
Graphics engineering
Dashboards
6
154 | 195
A6V11604297_en--_g
6. In the BASIC PROPERTIES, expand RACTIVE EDITOR and click OPEN EDITOR.
The RACTIVE EDITOR dialog box opens with the TEMPLATE tab displayed.
7. Paste the new HTML code in the TEMPLATE tab.
8. To scale the widget to fit the dashboard frame, change the width and height to 100% instead of px.
3. Adding a data source to the Energy and Water layers
A trended data point must be added to the Energy and Water layers to provide data for the comparison of the
building resource consumption to common household devices. Icons for the household devices do not display
until a trended data point has been added to the layer.
a. Adding a trend definition for online trended objects
If the trend is already defined, skip to
b. Adding a trended data point to the Energy and Water layers
.
Trends is selected in the core function pane.
1. Select > > Configure trend definitions > .
2. Navigate through the building hierarchy and select the object(s) to trend.
Only objects that currently do not have a trend definition are displayed.
3. Click Next.
4. Select the desired settings in the Trend data collection settings dialog box.
5. Click Apply to save the trend definition.