User Manual
Table Of Contents
- 1 About this document
- 2 Commissioning
- 2.1 Default connection
- 2.2 Initial login
- 2.3 Setup wizard
- 2.4 Discover and assign devices
- 2.5 Subscribing to the time master
- 2.6 Time synchronization of the time master
- 2.7 Registering as a foreign device
- 2.8 Touch panel settings
- 2.9 Operating and monitoring features
- 3 Data point integration
- 4 Graphic features
- 4.1 Plant view Tools
- 4.2 Kiosk graphics
- 4.3 Engineering notations
- 5 Graphics Builder
- 5.1 Overview
- 5.2 Pane tools
- 5.3 Graphics libraries
- 6 Graphics engineering
- 6.1 Using supersample graphics
- 6.2 Optimizing graphics for PXM touch panels and standard devices
- 6.3 Thumbnails
- 6.4 Dashboards
- 7 Advanced functionality
- 8 Tips and tricks
- 8.1 Updates required after a time zone change
- 8.2 APPLY BATCH TAGS
- 8.3 Graphic components within models cannot be modified
- 8.4 A graphic with relative binding that includes data points from different branches of the hierarchy cannot be created at the Root level
- 8.5 Relative hyperlinks cannot be added to a graphic at the Root level
- 8.6 Relative hyperlinks in a graphic are broken if the graphic is engineered offline and then imported to another device
- 8.7 Automatic logout from Desigo Control Point causes Graphics Builder to temporarily stop working
- 8.8 Detection of network interruptions
- 8.9 Cancelling a kiosk log out sequence
- 8.10 Special characters do not display in graphic file names
- 8.11 The color of a graphical component may display incorrectly if the component was copied
- Index
Graphics engineering
Using supersample graphics
6
A6V11604297_en--_g
145 | 195
Modifying the data point binding
This procedure creates a Relative by navName binding for the graphic components.
1. Individually select each component and smart label in the graphic, right-click, and select TOOLS >
RELATIVIZE.
The Component binding options dialog box displays.
2. In the Top Equip section, select a location in the building hierarchy where the graphic will be used.
The tool uses the Top Equip as the root when describing the relative location of the point within the
hierarchy.
3. Select the Relative: By navName radio button and click Apply.
4. Click to save your changes and Save to confirm the file name and location.
Note
Once you’re comfortable with the data point binding process, consider using the procedure Modifying the
binding option for multiple points [➙ 178].
Verifying the binding in the graphic
1. Individually select each component or smart label, right-click and select TOOLS > VIEW BINDINGS to view
the type of binding used. For example:
(point or shadowPoint) and navName=="Setpoint for cooling" is a relative binding.
baUniqueId=="9a0cffe8a0088543bfe4734dd93630bff4302fa7" is an absolute binding.
2. See Verifying relative binding queries [➙ 68] for the procedure to compare the graphic component bindings
to the navName tags displayed in the List view.
Continue with creating a thumbnail image and assigning the graphic to the Desigo Control Point device so that it
can be viewed.
Thumbnails [➙ 146]
Enable / disable graphics and kiosks [➙ 40]