User Manual
Table Of Contents
- 1 About this document
- 2 Commissioning
- 2.1 Default connection
- 2.2 Initial login
- 2.3 Setup wizard
- 2.4 Discover and assign devices
- 2.5 Subscribing to the time master
- 2.6 Time synchronization of the time master
- 2.7 Registering as a foreign device
- 2.8 Touch panel settings
- 2.9 Operating and monitoring features
- 3 Data point integration
- 4 Graphic features
- 4.1 Plant view Tools
- 4.2 Kiosk graphics
- 4.3 Engineering notations
- 5 Graphics Builder
- 5.1 Overview
- 5.2 Pane tools
- 5.3 Graphics libraries
- 6 Graphics engineering
- 6.1 Using supersample graphics
- 6.2 Optimizing graphics for PXM touch panels and standard devices
- 6.3 Thumbnails
- 6.4 Dashboards
- 7 Advanced functionality
- 8 Tips and tricks
- 8.1 Updates required after a time zone change
- 8.2 APPLY BATCH TAGS
- 8.3 Graphic components within models cannot be modified
- 8.4 A graphic with relative binding that includes data points from different branches of the hierarchy cannot be created at the Root level
- 8.5 Relative hyperlinks cannot be added to a graphic at the Root level
- 8.6 Relative hyperlinks in a graphic are broken if the graphic is engineered offline and then imported to another device
- 8.7 Automatic logout from Desigo Control Point causes Graphics Builder to temporarily stop working
- 8.8 Detection of network interruptions
- 8.9 Cancelling a kiosk log out sequence
- 8.10 Special characters do not display in graphic file names
- 8.11 The color of a graphical component may display incorrectly if the component was copied
- Index
Commissioning
Setup wizard
2
A6V11604297_en--_g
13 | 195
2.3 Setup wizard
The Setup wizard displays when you log in to any Desigo Control Point device with the status Unconfigured or
Download Required.
The Setup wizard is only available if the tool-free workflow has
always
been used with the device. If ABT Site
has been used
at any time
, the tool free commissioning wizard is not available.
The Desigo Control Point device restarts at the end of this procedure to save your
configuration settings in non-volatile memory.
Using the Setup wizard
1. Use the tables in this section to complete the Setup wizard.
2. At the final pane of the Setup wizard, click Save to complete the commissioning.
The device restarts and the login screen displays. The device is now available on the network.
Device fields
Fig. 1: Commissioning wizard, Device fields.
Setting
Description
Device name
(Required)
Name of the Desigo Control Point device. This name displays in the status bar.
Device instance number
(Required)
A unique number in the range from 0 through 4194302. The number must not be used
by any other device on the BACnet network.
Description
Text field to describe the device. This description displays in the work area.
Location
Text field to describe the device location.
Time zone
Drop-down list of global time zones.
Model name
(Information only)
Model number of the Desigo Control Point device.
Operation URL
(Information only)
IP address of the Desigo Control Point device.