User Manual
Table Of Contents
- 1 About this document
- 2 Commissioning
- 2.1 Default connection
- 2.2 Initial login
- 2.3 Setup wizard
- 2.4 Discover and assign devices
- 2.5 Subscribing to the time master
- 2.6 Time synchronization of the time master
- 2.7 Registering as a foreign device
- 2.8 Touch panel settings
- 2.9 Operating and monitoring features
- 3 Data point integration
- 4 Graphic features
- 4.1 Plant view Tools
- 4.2 Kiosk graphics
- 4.3 Engineering notations
- 5 Graphics Builder
- 5.1 Overview
- 5.2 Pane tools
- 5.3 Graphics libraries
- 6 Graphics engineering
- 6.1 Using supersample graphics
- 6.2 Optimizing graphics for PXM touch panels and standard devices
- 6.3 Thumbnails
- 6.4 Dashboards
- 7 Advanced functionality
- 8 Tips and tricks
- 8.1 Updates required after a time zone change
- 8.2 APPLY BATCH TAGS
- 8.3 Graphic components within models cannot be modified
- 8.4 A graphic with relative binding that includes data points from different branches of the hierarchy cannot be created at the Root level
- 8.5 Relative hyperlinks cannot be added to a graphic at the Root level
- 8.6 Relative hyperlinks in a graphic are broken if the graphic is engineered offline and then imported to another device
- 8.7 Automatic logout from Desigo Control Point causes Graphics Builder to temporarily stop working
- 8.8 Detection of network interruptions
- 8.9 Cancelling a kiosk log out sequence
- 8.10 Special characters do not display in graphic file names
- 8.11 The color of a graphical component may display incorrectly if the component was copied
- Index
Commissioning
Default connection
2
12 | 195
A6V11604297_en--_g
2 Commissioning
NOTICE
Changes to the Desigo Control Point device configuration are saved in non-
volatile memory every 30 minutes and whenever you log out of the device.
● Save and log out to immediately save changes to the device configuration.
● Changes to the device configuration are lost if a power cycle occurs within 30
minutes of the change and before you have logged out.
2.1 Default connection
Use the appropriate procedure for your configuration:
● Connecting through a BACnet/IP touch panel
● Connecting through a BACnet/IP Web interface
ⓐ Connecting through a BACnet/IP touch panel
Power and network cables are connected.
1. Tap to select a screen orientation.
2. Tap to display the Desigo Web login page.
ⓑ Connecting through a BACnet/IP Web interface
1. Connect to the USB port of the Desigo Control Point device.
2. Type the IP address 192.168.250.1 in the address bar of a browser.
The Desigo Web login page displays.
2.2 Initial login
1. Log in to the application using the Administrator account.
2. Enter one of the following passwords:
– Enter OneBT if the device status is Unconfigured. For example, a new device or after a firmware update.
– Enter the password selected during the previous configuration if the device status is Download
Required.
3. Change the password as required.
The Commissioning wizard displays to guide you through the device and network setup and application
activation.