User Manual

Safety notes
3
A6V11170804_en--_l 9 | 41
CAUTION
NEC (North
America)
Use of class 2 transformers limited to 100 VA or class 2 circuits at max. 100 VA
by a non-limited transformer of max. 400 VA, combined with overcurrent
protection (T 4 A fused) for each AC 24 V device. Multiple fuses for multiple
insulated secondary circuits per transformer are possible (see Power
requirements [ 28]).
The same applies to DC 24 V power supplies.
CAUTION
Device safety
Device-related safety is guaranteed, among others, by low voltage power supply
AC 24 V, DC 24 V and double insulation between the mains voltage AC 230 V,
AC 24 V circuits and the housing or Power over Ethernet (PoE Class 4).
Comply with specific regulations for electrical wiring per the following sections.
CAUTION
Grounding
(system neutral AC/DC 24 V)
Observe the following points when grounding AC 24 V (system neutral):
Operating voltage of AC 24 V is permitted in principle for both grounded as
well as non-grounded system neutrals. Local regulations and customs apply
accordingly. Grounding may be required or not allowed for functional reasons.
Recommendation: AC 24 V systems are generally grounded unless otherwise
not recommended by the manufacturer.
In order to avoid ground loops, connect systems with PELV to the ground at
one location only (especially for transformers), unless otherwise indicated.
The same applies to DC 24 V power supplies.
CAUTION
Functional ground
The connections of the functional earth must be connected on the installation side
with the building grounding system (PE).
CAUTION
Operating voltage AC/DC 24 V
It must meet requirements for SELV or PELV. Permissible deviation to nominal
voltage:
At the transformer/power unit: AC / DC 24 V -10 … + 20%
At the end device (web server): AC 24 V ±20%, DC 24 V ± 20%
At the end device (touch panel): AC 24 V ±20%, DC 24 V ± 20%