User Manual

Workflows
Tool-free commissioning of an operating and monitoring system
4
53 | 76
Siemens
A6V10429119_en--_a_07
Building Technologies
2018-12-19
Setting
Description
DHCP check box
If selected, DHCP is used to automatically configure IP addresses.
SNMP check box
If selected, SNMP monitoring is active.
Read community string
Community string that allows reading information from a device.
Network number
Number that identifies the network. Default: 0
UDP port
UDP Port number that the service uses to communicate. Default: 47808
Setting
Description
Network number
Number that identifies the network (MS/TP).
MAC address
MAC address for the device.
Max master
Set the Max master address to prevent the token being passed to unused MAC addresses
situated after the master (MS/TP).
Baud rate
Drop-down list of rates at which data is sent to the bus.