3.3 Resolving errors related to data point integration
Complete this procedure if a cache or integration error occurs.
1. Manually remove the device in ABT-SSA:
– Select > Setup & Service > Assigned devices.
– Select Assigned devices in the work area and click to open Edit mode.
– Click for the device with the error.
– Click Delete to confirm the action.
2. Re-add the device to the Assigned devices structure:
– Navigate to the Discovered devices structure.
– Click Discover to trigger a discovery and click OK to close the confirmation message.
– Select the check box for the device to be re-added.
– Click Copy.
– Navigate to Assigned devices and click Paste.
– Click to close Edit mode.
3. Repeat the data point integration process in Desigo Control Point:
– Select > > > > Data point integration.
– Select the check box for the device that requires data point integration.
– If necessary, change the template for the device by selecting a new value from the drop-down list.
– Click Integrate.