Purging an alarm routing
This procedure removes an alarm routing from the database.
Alarms is selected in the core function pane.
1. Select > > Configure alarm routing > .
The Purge alarm routings dialog box displays all alarm routings.
2. Select the alarm routing(s) to be removed and select Remove.
3. Select Apply to complete the removal.
2.8.8 Data point integration settings
Data point integration only displays under > Settings if a user role has been granted access to Tools.
The selections for Data point integration determine if data points from monitored automation stations are
automatically integrated to the application and how many BACnet objects are saved to the Desigo Control Point
device when data points are integrated.
Data point integration for newly assigned and updated devices
1. Select > > Data point integration.
2. Select or clear the options for newly assigned and updated devices. See the following table for more
information.
3. Set the Cache timeout.
4. Select or clear the option for integrating data points outside the building structure. See the following table for
more information.
5. Click Apply to save the settings.
Note
Each device manufacturer determines what type of update causes the BACnet database revision number to
change. Occasionally, you may find that data points from an updated device have not been automatically
integrated because the BACnet database revision number did not change. Should this happen, you must
manually reintegrate the data points through > > Data point integration.