User Manual
Commissioning
Operating and monitoring features
2
22 | 196
A6V11604297_en--_e
4. Use the Table
Alarm filter dialog box
to make selections in the second dialog box.
5. Click Apply to save your selections.
Setting
Description
Name
Name of the alarm routing configuration.
Default: Alarm routing
If a configuration is saved with the default name, subsequent default names are Alarm routing
n
.
Email subject
The email subject line for the routed alarm.
Default: Alarm notifications
Email recipients
Select one or more email addresses from the predefined list. Press CTRL and click to select
multiple items.
Default: No email addresses are selected
Select all contents check box
Select to include all the Contents fields in the routed emails.
Default: Check box is selected and all fields are included in the email.
Contents
A list of predefined alarm fields that can be included in the body of the email. Fields include:
● Initiating device
● Site
● Object name
● Priority
● Alarm state
● Date/Time
● Message text
Table 9: Configure alarm routing dialog box.
Setting
Description
Time range
Start
Route alarms that occur after this time on the selected day(s).
Default: 8:00 or 8:00 AM
Time is displayed in the format selected by the currently logged in user.
End
Route alarms that occur before this time on the selected day(s).
Default: 17:00 or 5:00 PM
Time is displayed in the format selected by the currently logged in user.
Days
Route alarms on the selected day(s) during the selected time range.
Default: No days are selected
Priority range
Priority or range of priorities where:
● Entering a single priority (for example, 100) only routes alarms or events of that priority.
● Entering a range of priorities (for example, 1-255) routes alarms or events within that range of
priorities
● Entering a selection of individual priorities (for example 100, 200, 255) only routes alarms or
events of these priorities.
Default: 1-255
Type
The type of alarm events that the email recipients receive. Options are:
● Alarm
● Event
● Acknowledgement/Reset
Default: All event types are selected
State
The alarm state values that the email recipients receive. Options are:
● Alarm
● Fault
● Return to normal
Default: All states are selected