Setting
Description
Name
Name of the alarm routing configuration.
Default: Alarm routing
If a configuration is saved with the default name, subsequent default names are Alarm routing
n
.
Email subject
The email subject line for the routed alarm.
Default: Alarm notifications
Email recipients
Select one or more email addresses from the predefined list. Press CTRL and click to select
multiple items.
Default: No email addresses are selected
Select all contents check box
Select to include all the Contents fields in the routed emails.
Default: Check box is selected and all fields are included in the email.
Contents
A list of predefined alarm fields that can be included in the body of the email. Fields include:
Initiating device
Site
Object name
Priority
Alarm state
Date/Time
Message text
Setting
Description
Time range
Start
Route alarms that occur after this time on the selected day(s).
Default: 8:00 or 8:00 AM
Time is displayed in the format selected by the currently logged in user.
End
Route alarms that occur before this time on the selected day(s).
Default: 17:00 or 5:00 PM
Time is displayed in the format selected by the currently logged in user.
Days
Route alarms on the selected day(s) during the selected time range.
Default: No days are selected
Priority range
Priority or range of priorities where:
Entering a single priority (for example, 100) only routes alarms or events of that priority.
Entering a range of priorities (for example, 1-255) routes alarms or events within that range of
priorities
Entering a selection of individual priorities (for example 100, 200, 255) only routes alarms or
events of these priorities.
Default: 1-255
Type
The type of alarm events that the email recipients receive. Options are:
Alarm
Event
Acknowledgement/Reset
Default: All event types are selected
State
The alarm state values that the email recipients receive. Options are:
Alarm
Fault
Return to normal
Default: All states are selected