User Manual
Commissioning
Operating and monitoring features
2
A6V11604297_en--_e
21 | 196
Setting
Description
Weekly
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
–
Monthly
Week 1 (Days 1-7)
Week 2 (Days 8-14)
Week 3 (Days 15-21)
Week 4 (Days 22-28)
Week 5 (Days 29-31)
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Time
Displayed in the format selected by the currently logged in user. The default setting is 22:00 or 10:00 PM.
● Field 1: Hours
● Field 2: Minutes
Table 7: Configure alarm history dialog box.
Alarm routing
Alarms is selected in the core function pane.
1. Select > > Alarm routing.
2. Use the following table to make selections in the Alarm routing dialog box.
3. To save your selections, click Apply.
Setting
Description
Max. number of resend attempts
The maximum number of times the application attempts to send an alarm notification email if the
alarm requires an acknowledgement and it has not yet been acknowledged.
If the object is no longer in alarm, an alarm notification email is not resent even if the alarm
requires an acknowledgement, but it has not yet been acknowledged.
Valid entries are numbers greater than or equal to 0. The default is 3.
Retry interval (minutes)
The number of minutes the application waits before resending an email for an unacknowledged
alarm.
Valid entries are numbers greater than or equal to 1. The default is 15.
Table 8: Configure alarm routing dialog box.
2.8.7 Configuring alarm notifications
This procedure configures alarm routing so that recipients only receive the notifications that apply to them. For
example, a selected list of recipients only receives emails for alarms that occur on weekends or during a specific
timeframe.
Prerequisites
● Email recipients are configured.
Configuring email recipients [➙ 17]
● Data points from the devices being monitored for alarms are integrated to the Desigo Control Point device.
Data point integration workflow
Alarms is selected in the core function pane.
1. Select > > Configure alarm routing > .
2. Use the Table
Configure alarm routing dialog box
to make selections in the first dialog box.
3. Click Next.