User Manual
Commissioning
Default connection
2
12 | 196
A6V11604297_en--_e
2 Commissioning
NOTICE
Changes to the Desigo Control Point device configuration are saved in non-
volatile memory every 30 minutes and whenever you log out of the device.
● Save and log out to immediately save changes to the device configuration.
● Changes to the device configuration are lost if a power cycle occurs within 30
minutes of the change and before you have logged out.
2.1 Default connection
Use the appropriate procedure for your configuration:
● Connecting through a BACnet/IP touch panel
● Connecting through a BACnet/IP Web interface
ⓐ Connecting through a BACnet/IP touch panel
Power and network cables are connected.
1. Tap to select a screen orientation.
2. Tap to display the Desigo Web login page.
ⓑ Connecting through a BACnet/IP Web interface
1. Connect to the USB port of the Desigo Control Point device.
2. Type the IP address 192.168.250.1 in the address bar of a browser.
The Desigo Web login page displays.
2.2 Initial login
1. Log in to the application using the Administrator account.
2. Enter one of the following passwords:
– Enter OneBT if the device status is Unconfigured. For example, a new device or after a firmware update.
– Enter the password selected during the previous configuration if the device status is Download
Required.
3. Change the password as required.
The Commissioning wizard displays to guide you through the device and network setup and application
activation.