Assortment / System Description

10 PXC7 automation stations
Freely programmable automation stations for HVAC, building services plants,
and system controllers
BTL tested BACnet communication on IP (BACnet/IP and BACnet/SC) or
BACnet MS/TP, in compliance with the BACnet standard including B-BC profile
(Rev. 1.15)
Modbus TCP / RTU and BACnet MS/TP
IT security including HTTPS and BACnet/SC (as BACnet/SC hub)
WLAN interface for engineering and commissioning
System functions such as alarming, schedulers, trending, time sync, and life
check
Grouping functionality e.g. common setpoints for room controls or energy
demand
System functionality for integrated subsystem and devices
Integration of Modbus subsystems and devices via TCP and/or RTU: Data point
mapping to BACnet/IP and supervisory functionality
Integration of BACnet MS/TP subsystems and devices: Supervisory functionality
and routing to BACnet/IP
Function PXC7.E400S PXC7.E400M PXC7.E400L
Number of inputs/outputs via TXM modules 100 200 400
Number of integration data points
(Modbus TCP and Modbus RTU)
100 200 400
Total number of inputs/outputs TXM and
integration data points
100 250 600
Number of configurable RS485 interfaces for
Modbus or BACnet MS/TP for field level networks
1 2 4
Number of MS/TP devices per field level network
(basic principle: 60 devices per trunk)
60
1)
2 x 60
1)
2 x 60
1)
Number of BACnet/SC nodes connected 200 200 200
1)
Depending on the behavior of the third-party MS/TP devices
For more information about PXC7 automation stations, refer to the data sheet
A6V12505052.
PXC7 automation stations
10