Assortment / System Description

9 PXC5 system controllers
Freely programmable system controller that integrate Modbus and/or MS/TP
devices or subsystems.
BTL tested BACnet communication on IP (BACnet/IP and BACnet/SC) or
BACnet MS/TP, in compliance with the BACnet standard including B-BC profile
(Rev. 1.15)
Modbus TCP / RTU and BACnet MS/TP
IT security including HTTPS and BACnet/SC (as BACnet/SC hub)
WLAN interface for engineering and commissioning
System functions such as alarming, schedulers, trending, time sync, and life
check
Grouping functionality e.g. common setpoints for room controls or energy
demand
System and supervisory functionality
Integration of Modbus subsystems and devices via TCP and/or RTU: Data point
mapping to BACnet/IP and supervisory functionality
Integration of BACnet MS/TP subsystems and devices: Supervisory functionality
and routing to BACnet/IP
Function PXC5.E003
Number of configurable RS485 interfaces for Modbus or BACnet
MS/TP integration in field level networks
2
Number of Modbus data points via RTU and / or TCP 500
Number of MS/TP devices
(basic principle: 60 devices per trunk)
2 x 60
1)
Number of connected BACnet/SC nodes 100
1)
Depending on the behavior of the third-party MS/TP devices
For more information about PXC5 system controllers, refer to the data sheet
A6V11646020.
PXC5 system controllers
9
14 | 20 A6V13054432_en--_a