Assortment / System Description
Table Of Contents
- Table of Contents
- 1 Desigo PXC Controllers – The flexible, reliable ...
- 2 ... and scalable automation and control system
- 3 Desigo Control Point ...
- 4 ... Embedded building operations
- 5 ... Portfolio
- 6 Operation and monitoring
- 7 A family of programmable automation stations
- 8 PXC4 automation stations
- 9 PXC5 system controllers
- 10 PXC7 automation stations
- 11 TXM input/output modules for PXC7 and PXC4
- 12 ABT Site ... for flexible and intuitive…
- 13 ... set-up, programming, and commissioning
- 14 Can be extended in stages at any time
8 PXC4 automation stations
For the control of primary plants.
● Compact automation station for HVAC and building control systems, freely
programmable
● System functions such as alarming, schedulers, trend functions, and access
security
● Stand-alone application or for use within a building automation and control
system
● Direct connection of field devices
● Extensions possible with TXM I/O modules
● Integration of communicative field devices, e.g. variable speed drives via Modbus
● Engineering and commissioning with the user-friendly ABT Site tool
● BTL tested BACnet communication on IP (BACnet/IP and BACnet/SC) or
BACnet MS/TP, in compliance with the BACnet standard including B-BC profile
(Rev. 1.15)
● WLAN interface for engineering and commissioning
● BACnet/SC support (as BACnet/SC node only)
Function PXC4.E16
1)
PXC4.E16S
Number of inputs/outputs (onboard) 16 16
Number of universal inputs / outputs (UIO) 12 12
Number of relay outputs (DO) 4 4
Number of inputs/outputs (onboard + TXM) 40 40
Number of Modbus data points TCP and/or RTU 40 0
Number of BACnet/SC nodes connected
PXC4.E16, PXC4.E16S
0
(node only)
0
(node only)
1)
Communication BACnet/IP, BACnet/SC: PXC4.E16 and PXC4.E16S.
Communication BACnet MS/TP: PXC4.M16 and PXC4.M16S
For more information about PXC4 automation stations, refer to the data sheets
A6V11646018 and A6V11937668.
UIO Universal inputs/outputs support the following signal types:
● Passive sensors LG-Ni 1000, 2x LG-Ni1000, Ni 1000 DIN, Pt 1000
(375, 385), NTC 10k, NTC 100k
● Resistance sensors 1000 Ohm, 2500 Ohm, 2650 Ohm,1000...1175
Ohm (for setpoint shift)
● Active sensors DC 0 ... 10 V.
● Binary potential-free contacts for signaling functions
● Counters to 25 Hz (electronic switch to 100 Hz)
● Analog outputs DC 0...10 V
DO Relay outputs AC 250 V for binary controls, changeover contact (NO,
NC, pulse)
PXC4 automation stations
8
A6V13054432_en--_a 13 | 20