Assortment / System Description

8 PXC4 automation stations
For the control of primary plants.
Compact automation station for HVAC and building control systems, freely
programmable
System functions such as alarming, schedulers, trend functions, and access
security
Stand-alone application or for use within a building automation and control
system
Direct connection of field devices
Extensions possible with TXM I/O modules
Integration of communicative field devices, e.g. variable speed drives via Modbus
Engineering and commissioning with the user-friendly ABT Site tool
BTL tested BACnet communication on IP (BACnet/IP and BACnet/SC) or
BACnet MS/TP, in compliance with the BACnet standard including B-BC profile
(Rev. 1.15)
WLAN interface for engineering and commissioning
BACnet/SC support (as BACnet/SC node only)
Function PXC4.E16
1)
PXC4.E16S
Number of inputs/outputs (onboard) 16 16
Number of universal inputs / outputs (UIO) 12 12
Number of relay outputs (DO) 4 4
Number of inputs/outputs (onboard + TXM) 40 40
Number of Modbus data points TCP and/or RTU 40 0
Number of BACnet/SC nodes connected
PXC4.E16, PXC4.E16S
0
(node only)
0
(node only)
1)
Communication BACnet/IP, BACnet/SC: PXC4.E16 and PXC4.E16S.
Communication BACnet MS/TP: PXC4.M16 and PXC4.M16S
For more information about PXC4 automation stations, refer to the data sheets
A6V11646018 and A6V11937668.
UIO Universal inputs/outputs support the following signal types:
Passive sensors LG-Ni 1000, 2x LG-Ni1000, Ni 1000 DIN, Pt 1000
(375, 385), NTC 10k, NTC 100k
Resistance sensors 1000 Ohm, 2500 Ohm, 2650 Ohm,1000...1175
Ohm (for setpoint shift)
Active sensors DC 0 ... 10 V.
Binary potential-free contacts for signaling functions
Counters to 25 Hz (electronic switch to 100 Hz)
Analog outputs DC 0...10 V
DO Relay outputs AC 250 V for binary controls, changeover contact (NO,
NC, pulse)
PXC4 automation stations
8
A6V13054432_en--_a 13 | 20