Data Sheet for Product
9
Siemens Schweiz AG A6V11937668_en--_g
Smart Infrastructure 2022-02-18
Digital input
Contact query voltage 21.5...25V
Contact query current 1mA; 6 mA initial current
Contact resistance for closed contacts Max. 200Ω
Contact resistance for open contacts Min. 50kΩ
Counter memory (counter inputs 0 ... 4.3 x 10
9
(32-bit counter)
Min. closing/operating time [ms]
including bounces
Of which
Max. bounce time [ms]
Max. counter frequency
(symmetrical)
BI NO / BI NC 60 20
BI Pulse NO 30 10
CI Mech (25Hz) 20 10 25 Hz
CI El (100Hz) 5 0 100 Hz
Outputs
Analog output
Type Range (over range) Resolution Output current
AO 0-10V 0...10V (-0.05…10.6V) 1mV Max. 1mA
AO 0-10V
standard
0...100%
0% = 0 V, 100% = 10V
(-0.05...10.6 V)
0.01% Max. 1mA
Relay output (outputs DO1...DO4)
External supply line fusing
Non-renewable fuse
Circuit breakers
Max. 10 A, slow
Max. 13 A, characteristic B, C, D as per EN60898
Switching voltage AC/DC Max. AC 250 V / DC 30 V
Min. AC/DC 12 V
Current load AC NO contact: Max. 4 A resistive, 3 A inductive (cos phi
0.6)
NC contact: max. 2 A resistive, 1.5 A inductive (cos phi
0,6)
Min. 1 mA at AC 250 V
Min. 10 mA at AC 12 V
Current load DC NO contact: Max. 3A resistive at DC 30V
NC contact: Max. 1A resistive at DC 30V
Min. 10 mA resistive at DC 12V
Switch-on current NO contact: Max. 10A (1s)
NC contact: Max. 3A (1s)
Response/release time 7ms / 3ms typical
Contact life at AC 250 V (reference values)
At 0.3 A resistive
NO contact at 3A resistive
NC contact at 2A resistive
Reduction fact at ind. load (cos phi = 0.6)
5 x 10
5
switchings
1 x 10
5
switchings
1 x 10
5
switchings
0.6
Insulating strength between relay contacts and system
electronics (reinforced insulation).
AC 3750V, as per EN 60730-1
Field device supply (Onboard)
AC 24V (terminal V~) Max. 2A, short-circuit proof *)
DC 24V (terminal V+) Max. 100mA, short-circuit proof, protected against
incorrect wiring with AC 24V