Data Sheet for Product

12
Siemens Schweiz AG A6V11937668_en--_g
Smart Infrastructure 2022-02-18
Connection terminals
65 66 67 68 69 70
3 4
5 6 7
8 9
Terminal Symbol Description Module Channel
3, 4 KNX PXC4.M16: KNX PL-Link (for future use)
5, 6 24 V ~, Operating voltage AC 24 V
7 Functional ground (must be connected on the installation
side with the building grounding system (PE).
8 to 29 Ux Universal inputs/outputs 61 1…12
Measuring ground for Ux
8, 19 V+ DC 24V power for field devices 2.4W / 100mA
18, 29 V~ AC 24V power for field devices 48VA / 2A
65, 66, 67 MSTP PXC4.M16: Interface EIA-485 (BACnet MS/TP)
68, 69, 70 COM
MSTP
PXC4.M16: Interface EIA-485 (Modbus RTU)
PXC4.M16S: Interface EIA-485 (BACnet MS/TP)
Term on, off Switch for bus connection
Polar on, off Switch for polarization
75 to 86 DOx Relay outputs 11 1…4
Wiring lines for field devices
Wiring length max. 300 m (1,000ft), CU wire or CU strand.
Cross-section depending on the signal
30m (100ft) applies for signal types AI NTC10K and AI NTC100K
or 80m (260ft) with shielding
Examples of connection diagrams for universal inputs/outputs
Digital inputs
Ux
Ux
S1
S2
Feedback contact (NO)
Feedback contact (NC)
Count inputs: Counter inputs, that count faster than 1 Hz and are laid with more than 10 meters using analog inputs in
the same cable duct, must be shielded.