Data Sheet for Product

5
Siemens Schweiz AG A6V11646018_en--_g
Smart Infrastructure 2022-02-18
LED displays
Activity LED Color Activity Function
Ethernet 1/2 Green Continuously ON
Continuously OFF
Flashing
Link active
No connection
Network traffic
Yellow Continuously ON
Continuously OFF
Link 100
Link 10 Mbps
RUN Green Continuously ON
Continuously OFF
Flashing
Device operational
Device not operational
Start-up or program halted
Red Continuously OFF
Continuously ON
Rapid flashing
OK
HW or SW fault
Firmware or application missing/corrupted
Blue Continuously ON
Continuously OFF
Connection to the cloud OK
No connection to the cloud
COM TX
(PXC4.E16)
Yellow Flashing
Continuously OFF
Communication
No communication to subsystem
COM RX
(PXC4.E16)
Yellow
SVC Red Continuously OFF
Flashing
OK
Device is not configured
Flashing per wink
command
Identification of the device after receipt of
wink command
2s
1s
5 Hz 5 Hz
2s
1s
WLAN Blue Steady OFF
Steady ON
Flashing
WLAN inactive
WLAN active and at least one WLAN client
connected
WLAN active and no WLAN client
connected
Service button Short press (< 1 s)
Long press (> 3 s)
Identification in the network
Enable / disable WLAN
WLAN is disabled automatically after 10
min if no client is connected
As per description Do the following to reset the device to
factory state:
1. Power off the device.
2. Power on the device.
3. Wait until all LEDs light up and turn off
again, then press the Service button.
4. Keep the Service button pressed until
all LEDs light up, then release the
button.
All LEDs go off, the device restarts.
5. Wait until the device has fully started –
unconfigured (green RUN LED and
red SVC LED are flashing)