Data Sheet for Product
10/18
Siemens PXC….D – Automation stations, compact model CM1N9215en_25
Smart Infrastructure 2022-01-15
PXC22.1.D
1, 2
24 V ~,
Operating voltage AC 24 V
3 Functional earth CFC IOAddr
4 … 21
DO1 … DO6
6
Digital outputs (Relays)
DO1: C=5.1
28, 29
CLA, CLB
L
ON
W
ORKS
bus
30 ... 38
U1 … U6
6 Universal inputs / outputs with Q250
xx1: C=4.1 *)
39 ... 61
U7 … U16
1
0
Universal inputs / outputs
xx7: C=1.1 *)
80, 81
CP+, CP
–
PPS2 bus (for up to 5
QAX... room units)
82 ... 84
, CD, CS Island bus: Additionally, the system neutral conductor
of the
island bus system must be connected to
(Terminal 82).
C
HMI
RJ45 socket for PXM10, PXM20
D
HMI / Tool
RJ45 socket for PXM10, PXM20 and tool
PXC36.1.D
1, 2
24 V ~,
Operating voltage AC 24 V
3 Functional earth CFC IOAddr
4 … 27
DO1 … DO8
8 Digital outputs (Relays)
DO1: C=5.1
28, 29
CLA, CLB
L
ON
W
ORKS
bus
30 ... 38
U1 … U6
6 Universal inputs / outputs
with
Q
250
xx1: C=4.1 *)
39 ... 73
U7 … U24
18 Universal inputs / outputs
xx7: C=1.1 *)
74 ... 79
DI1 … DI4
4 digital inputs
DI1: C=3.1
80, 81
CP+, CP
–
PPS2 bus (for
up to 5
QAX... room units)
82 ... 84
, CD, CS Island bus: Additionally, the system neutral conductor
of the
island bus system must be connected to
(Terminal 82).
C
HMI
RJ45 socket for PXM10, PXM20
D
HMI / Tool
RJ45 socket for PXM10, PXM20 and tool
*) Signal type when no application is loaded (wiring test):
U1…U6: xx = Y10S, U7…U24: xx = R1K
Observe the technical data for the relay outputs.
Local installation regulations must be observed.
HMI / TOOL
DO1
U1 U2U3 U4
U5 U6U7 U8
U9 U10 U11 U12
U13 U14 U15 U16
HMI / TOOL
DO1
U1 U2 U3 U4
U5 U6 U7 U8
U9 U10 U11 U12
U13 U14 U15 U16
U17
U18
U19
U20
U21
U22
U23
U24
9
2
1
5
A
2
2
_
0
2
STOP
Caution!