s 9203mmP01 9 203 Desigo™ Room automation Room automation stations · · · · · · · · · · CM1N9203en_08 2020-10-30 PXC3.E... Modular, programmable room automation stations for HVAC, lighting, and shading. BACnet / IP communications; BACnet profile AAC (BTL label). Optional island bus (including bus power supply) to connect TX-I/O modules with any data point mix. Optional KNX PL-Link peripheral bus (including bus power supply) to connect sensors, actors and room units.
Use PXC3 series room automation stations can be used for buildings with more sophisticated requirements on functionality and flexibility. Desigo Room Automation is used when several disciplines (HVAC, lighting, shading) are combined to form one solution and when high flexibility is required. Desigo Room Automation is perfect for solutions optimizing energy (class A) without loss of comfort. Functions Control of several rooms A PXC3 series room automation station can assume control for multiple rooms.
Communications · The room automation stations have a 2-port Ethernet switch to support for lowcost cabling via line topology. · A USB Device port is available for service and commissioning. · TX-I/O modules connected directly to the PXC3 allow for direct connection of field devices. This offers maximum flexibility. · The KNX PL-Link peripheral bus supports room operator units, sensors, and actuating devices.
Mechanical design The compact build allows for mounting the devices on a standard mounting rail.
RUN 9203z02 LED indicators (depending on the type) LED Color RUN Green FLT Red IB Yellow PL Yellow Continuously ON Flashing Continuously OFF DALI Yellow SVC Red Continuously ON Continuously OFF Flashing Blinking per IDENTIFY DEVICE command Continuously OFF Blinking Blinking per wink command*) Continuously ON Continuously OFF Flashing Continuously ON Continuously OFF FLT IB PL DALI SRV 1) 2) 87654321 9270Z05 1) Service pin 2) Service pin DALI Activity Continuously ON Continuously OFF Flas
Product documentation · · · · · Engineering and commissioning: See ABT online help. Planning manual Desigo Room automation, CM111043. TX-I/O planning and installation manual, CM110562. Application Guide for IP Networks in Building Automation Systems, CM110668. Desigo Technical principles CM110664, chapters 18 and 26. Engineering Caution! · Each device has a unique serial number for commissioning support.
Installation See planning manual Desigo Room automation, CM111043. STOP Island bus Polarity: If a TXS1.12F10 supply module is connected to output 24 V, do not invert ~ and ^. The devices are not damaged but island bus communications will not work. Note! Operation If island bus or USB communications do not work, this is an indicator that the AC 24 V operating voltage is incorrectly wired (conductors ~ and ⏊ inverted).
Ethernet interface Plug Interface type Bit rate Protocol 2 x RJ45, screened 100BaseTX, IEEE 802.3 compatible 10 / 100 Mbps, autosensing BACnet over UDP/IP USB interface Plug Data rate Galvanic isolation of ^ Protective circuit against surges and over current Type B (USB device) 12 MBit/s (Full speed) No Yes (balancing currents are limited, also in the GND conductor) Interface type Nominal voltage Max.
Wiring, topology, cable length, cross section Connection terminals, plug-in See planning manual Room automation, CM111043. Construction type Copper-wire or Cu-stranded with wire end sleeve Copper-stranded without wire end sleeve Screwdriver Max. tightening torque Assignment as per EN 60730 Housing protection standard Ambient conditions Standards, directives and approvals Pluggable screw terminals 1 x 0.6 mm dia. to 2.5 mm2 or 2 x 0.6 mm dia. to 1,0 mm2 1 x 0.6 mm dia. to 2.5 mm2 or 2 x 0.6 mmÆ to 1.
Disposal The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage. · Dispose of the device through channels provided for this purpose. · Comply with all local and currently applicable laws and regulations.
Basic circuit diagram (connections AC 24 V, fusing) 1 + 2 4 3 ~ KNX 2) 24V/2A 5 ~ 6 24V~ 7 ~ 8 24V~ PTC KNX Island bus CS M 10A 9 1), 2) 3) 10 11 + DALI 3) 12 Island Bus 1) 9203z05_02 DALI V~ Not with PXC3.E16A… types Only with PXC3.E....A... types 11 / 12 Siemens Smart Infrastructure PXC3.E...
Dimensions 9203M01 All dimensions in mm Published by: Siemens Switzerland Ltd. Smart Infrastructure Global Headquarters Theilerstrasse 1a 6300 Zug Switzerland Tel. +41 41-724 24 24 www.siemens.com/buildingtechnologies © Siemens Switzerland Ltd 2012 Delivery and technical specifications subject to change 12 / 12 Siemens Smart Infrastructure PXC3.E...