Data Sheet for Product
2 / 12
Siemens PXC3.E... Room automation stations CM1N9203en_08
Smart Infrastructure 2020-10-30
Use
PXC3 series room automation stations can be used for buildings with more
sophisticated requirements on functionality and flexibility.
Desigo Room Automation is used when several disciplines (HVAC, lighting,
shading) are combined to form one solution and when high flexibility is required.
Desigo Room Automation is perfect for solutions optimizing energy (class A)
without loss of comfort.
Functions
A PXC3 series room automation station can assume control for multiple rooms.
These programmable room automation stations provide the infrastructure to
provide and process system- and application-specific functions.
Desigo
version
Product No.
Stock No.
Function Number of I/O
data points
KNX PL-
Link
TX-I/O modules DALI bus
V7
PXC3.E16A-200A
S55376-C177
DALI applications
only
90
2)
- - - -
DALI-2
max. 64 ballasts
3)
and max. 63 input
devices
4)
On-board bus
power
supply: 230 mA
PXC3.E72A-200A
S55376-C178
typically 4 rooms
typically 8 room
segments
1)
140
2)
max. 64
devices
max. 72 physical
I/O points
PXC3.E75A-200A
S55376-C179
typically 8 rooms
typically 16 room
segments
1)
280
2)
max. 64
devices
max. 200 physical
I/O points
V6
PXC3.E16A-100A
S55376-C118
DALI applications
only
64
2)
- - - -
DALI
max. 64 ballasts
3)
On-board bus
power
supply: 128 mA
PXC3.E72-100A
S55376-C130
typically 4 rooms
typically 8 room
segments
1)
140
2)
max. 64
devices
max. 72 physical
I/O points
- -
PXC3.E72A-100A
S55376-C131
typically 4 rooms
typically 8 room
segments
1)
140
2)
max. 64
devices
max. 72 physical
I/O points
DALI
max. 64 ballasts
3)
On-board bus
power
supply: 128 mA
PXC3.E75-100A
S55376-C132
typically 8 rooms
typically 16 room
segments
1)
280
2)
max. 64
devices
max. 200 physical
I/O points
- -
PXC3.E75A-100A
S55376-C133
typically 8 rooms
typically 16 room
segments
1)
280
2)
max. 64
devices
max. 200 physical
I/O points
DALI
max. 64 ballasts
3)
On-board bus p
ower
supply: 128 mA
1)
Architectural building grid (also called room axis).
2)
Total number of data point used by TX-I/O, KNX PL-Link and DALI.
For details see Desigo Technical principles CM110664, chapter 18.
3)
For commercially available DALI -ballasts up to 64 DALI addresses are
supported.
4)
For commercially available DALI-2 input devices up to 63 DALI-2 addresses are
supported.
Note! The current consumption of the connected DALI ballasts and input
devices must not exceed the guaranteed bus supply current of the PCX3.
The DALI bus power supply may limit number of connectable DALI devices.
See Planning manual, CM111043.