Operating Instructions

Table Of Contents
Chapter 2Hardware Features
HOA (Hand-Off-Auto) Upgrade Kits
0
| 118
Siemens Industry, Inc.
Owner's Manual
553-104
Building Technologies
2018-10-01
The HOA module can be used to override outputs and monitor inputs.
The HOA mapping and definition of a logical point in the database can be done in
any order.
The HOA is hot-swappable. The module can be installed without powering down
the controller and interrupting facility operations.
The HOA module can also be remote mounted on the inside or outside of an
enclosure door, using an optional accessory sold separately.
The firmware provides a default HOA switch assignment based on the type of the host
field panel. There are new menus available that allow for the identification of what HOA
module is connected and communicating, along with the ability to view and customize
the HOA switch mapping.
HOA Specifications
Electrical
Power Consumption
Baud rate
5 V/60 mA
(from host controller)
38400
Dimensions
(L x W x D)
5.65 in. × 1.8 in. × 0.68 in.
(14.4 cm × 4.6 cm × 1.7 cm)
Weight
8 Switch
16 Switch
0.12 lb
0.14 lb
Operating Environment
Ambient Operating Temperature
Ambient Operating Temperature for rooftop (extended
temperature model)
Shipping and Storage
23°F to 122°F (-5°C to 50°C)
-40°F to 158°F (-40°C to 70°C)
-13°F to 167°F(-25°C to 70°C)
Agency Listings
UL Listing
cUL Listed
FCC Compliance
WEEE
RoHS
UL864 UUKL (except rooftop model)
UL864 UUKL7 (except rooftop model)
CAN/ULC-S527-M8 (except rooftop model)
UL 916 PAZX (all models)
Canadian Standards C22.2 No. 205-M1983, PAZX7
47 CFR Part 15