Chapter 2—Hardware Features
BACnet Compact Series Specifications
0
47 |
118
Siemens Industry, Inc.
Owner's Manual
553-104
Building Technologies
2018-10-01
Electrical
Digital Input
Contact Closure Sensing
Dry Contact/Potential Free inputs only
Does not support counter inputs
Digital Output Class 1 Relay
Analog Output 0 to 10 Vdc
Universal Input (UI) and Universal
Input/Output (U)
Analog Input
Voltage (0-10 Vdc)
Current (4-20 mA)
1K Ni RTD @ 32°F
1K Pt RTD (375 or 385 alpha) @ 32°F
10K NTC Type 2 or Type 3 Thermistor @ 77°F
100K NTC Type 2 Thermistor @ 77°F
Digital Input
Pulse Accumulator
Contact Closure Sensing
Dry Contact/Potential Free inputs only
Supports counter inputs up to 20 Hz
Analog Output (Universal Input/Output (U) points only)
Voltage (0-10 Vdc)
Super Universal (X)
Analog Input
Voltage (0-10 Vdc)
Current (4-20 mA)
1K Ni RTD @ 32°F
1K Pt RTD (375 or 385 alpha) @ 32°F
10K NTC Type 2 or Type 3 Thermistor @ 77°F
100K NTC Type 2 Thermistor @ 77°F
Digital Input
Pulse Accumulator
Contact Closure Sensing
Dry Contact/Potential Free inputs only
Supports counter inputs up to 20 Hz
Analog Output
Voltage (0-10 Vdc)
Current (4-20 mA)
Digital Output (requires
an external relay)
0 to 24 Vdc, 22 mA max.
Operating Environment
Ambient operating temperature 32°F to 122°F (0°C to 50°C)
Ambient operating temperature
with rooftop
(extended temperature) option
-40°F to 158°F (-40°C to 70°C)
Relative Humidity PXC
-16 and
PXC
-24:
5 to 95% rh non-condensing
PXC
-36:
5 to 95% rh non-condensing
Mounting Surface PXC
-16 and
PXC
-24:
Direct equipment mount, building wall, or structural member
PXC
-36:
Building wall or a secure structure