Chapter 2Hardware Features
Communication Connections
0
| 118
Siemens Industry, Inc.
Owner's Manual
553-104
Building Technologies
2018-10-01
NOTE:
A P1 FLN license must be installed in order to use Wireless FLN.
NOTE:
The PXC Compact on P1 is not supported on the Wireless FLN.
The following additional hardware is required to implement the Wireless P1 FLN with
the PXC Compact Series:
Field Level Network Transceiver (FLNX)
Field Panel Transceiver (FPX)
See the section Minimum Firmware Revision Required for information on the firmware
revision required to implement Wireless P1 FLN.
PXC Compact on P1
The PXC-16 and the PXC-24 may be configured to reside on the P1 Field Level
Network (FLN). When configured for the FLN, the PXC Compact functions as a
programmable FLN device, which accepts custom applications.
Virtual AEM
Without additional hardware, the Virtual AEM connects an RS-485 APOGEE
Automation Level Network (ALN) or individual RS-485 field panels to a P2 Ethernet
network.
An additional license is required.
USB Host Port
The USB host port supports a USB printer and connection to a modem through a USB-
to-RS-232 adapter. A USB hub may be used to support both a printer and modem on
the USB host port.
On a BACnet/IP ALN, the USB Host port provides support for service modems and
line printers.
On an Ethernet TCP/IP or RS-485 ALN, the USB Host port provides support for
dial-up or service modems and line printers.
TX-I/O Island Bus
The PXC-36 offers the flexibility of expanding the total point count through a self-
forming island bus. With the addition of TX-I/O modules and a TX-I/O Power Supply,
up to 32 points (or four TX-I/O modules) can be supported.
An additional license may be required to enable the Island Bus.