Chapter 2—Hardware Features
Compact Series Backup Batteries
0
34
| 118
Siemens Industry, Inc.
Owner's Manual
553-104
Building Technologies
2018-10-01
PXC-36 Supported Point Types.
Configurable Points
Dedicated Points
Point Type
Super Universal
(X)
Points 1-6
Universal
Input/Output (U)
Points 7-24
Digital Input (DI)
Points 25-28
Digital Output
(DO)
Points 29-36
Digital
Output
Binary/Digital Output
•
4
•
1)
Platinum 1K 375 or 385 alpha.
2)
Siemens, Johnson Controls, and DIN Standard Nickel.
3)
10K and 100K Type 2 and 10K Type 3.
4)
Requires an external relay.
5)
Sensor supply 24 Vdc, 4.8W
Compact Series Backup Batteries
The PXC Compact Series contains one non-rechargeable AA (LR6) battery and one
non-rechargeable coin cell (BR2032) battery that serve as a power backup in the event
of a power failure. The batteries only discharge during a power loss. They do not
recharge.
CAUTION
Only use a 3.6 Volt lithium battery in PXC Compact models with extended
temperature range operation.
Only use a 1.5 Volt alkaline battery in standard
PXC Compact models.
• The 3.6 Volt lithium battery is designed to operate at both high and low temperature
extremes, and it provides a long service life in an extended temperature environment.
• The 1.5 Volt alkaline battery is not guaranteed to provide backup protection in
models with extended temperature range operation, even if the controller is operating
in a room-temperature environment.
• If a 3.6 Volt lithium battery is used in standard PXC Compact
models, the battery
quickly discharges and provides much less backup protection than a 1.5 Volt alkaline
battery.