Chapter 1—Introduction
APOGEE Automation Networking
22
| 118
Siemens Industry, Inc.
Owner's Manual
553-104
Building Technologies
2018-10-01
Figure 1: Figure. Commanding Over an Automation Level Network.
RS-485 P2 Automation Level Network
The RS-485 ALN is a proprietary token-passing network that communicates over RS-
485 cabling. It is Protocol 3 (P3) at and above 38,400 bps, and Protocol 2 (P2) below
38,400 bps.
● An Insight workstation is optional with this ALN.
● Up to 100 field panels (99 with an Insight workstation) can be connected and can
communicate by means of an RS-485 peer-to-peer network.
● Information can be sent and retrieved across the RS-485 ALN from any connected
field panel.