Chapter 2—Hardware Features
PXC Compact on P1
0
72
| 118
Siemens Industry, Inc.
Owner's Manual
553-104
Building Technologies
2018-10-01
Commanding Points
Do the following to change the point value and command the points in the field panel.
These steps also apply to commanding TEC subpoints.
Figure 21: Point Action Command Submenu
Menu/Submenu
Step
Description
Main Rotate
DIAL
to highlight
Points
.
Press
DIAL
/
OK
to select
Points.
Displays the Points menu.
Points
Press
DIAL
/
OK
to highlight
desired point.
Displays the Point Action Command submenu.
Point Action
Rotate
DIAL
to highlight
Command
.
Press
DIAL
/
OK
to select
Command
.
Displays the point name in title. Lists the selected point’s
current value, edit (highlighted) and priority fields.
[selected point name]
With
Edit
field highlighted,
rotate
DIAL
to each numeric
character and decimal, and
press
DIAL
/
OK
after each
numeric increment, including
decimal character, until you
enter the new value.
Changes the specified point value.
Press
DIAL
/
OK
.
Confirms the point value change and moves to the Priority
field.
With
Priority
field highlighted,
repeat steps to change priority
of selected point.
NOTE:
This
field is BACnet-specific. P2
firmware always commands at
a priority of OPER.
Confirms the point priority change and returns you to the
Points menu.
Press
ESC
.
Returns you to the previous menu without changing the
point value or priority.