Data Sheet for Product
PXC Compact Series
Compact Series Specifications
6
Siemens Industry, Inc. 149-454
Smart Infrastructure 2020-05-20
Electrical
Power Requirements
24 Vac ±20% input @
50/60 Hz
Power Consumption (Maximum)
PXC-16: 18 VA @
24 Vac
PXC-24: 20 VA @ 24 Vac
PXC-36: 35 VA 24 Vac
AC Power and Digital Outputs
NEC Class 1 Power Limited
Communication and all other I/O
NEC Class 2
Digital Input
Contact Closure Sensing
Dry Contact/Potential Free inputs only
Does not support counter inputs
Digital Output
Class 1 Relay
Analog Output
0 to 10 Vdc
Universal Input (UI) and Universal
Input/Output (U)
Analog Input
Voltage (0-10 Vdc)
Current (4-20 mA)
1K Ni RTD @ 32°F
1K Pt RTD (375 or 385 alpha) @ 32°F
10K NTC Type 2 or Type 3 Thermistor @ 77°F
100K NTC Type 2 Thermistor @ 77°F
Digital Input
Pulse Accumulator
Contact Closure Sensing
Dry Contact/Potential Free inputs only
Supports counter inputs up to 20 Hz
Analog Output (Universal Input/Output (U) points only)
Voltage (0-10 Vdc)