Chapter 2—Hardware Features
PXC Compact on P1
0
56
| 118
Siemens Industry, Inc.
Owner's Manual
553-104
Building Technologies
2018-10-01
Default Applications
Both the PXC-16 and PXC-24 support a default (slave mode) application, which is
useful if a custom application has not yet been loaded into the PXC Compact on P1 in
an Application ISB file.
● If a PXC Compact is set up in P1 mode without an application number, the default
application is used.
● For the PXC-16 the default application is 3916; for the PXC-24, the default
application is 3924.
● AI and DI points in all applications can only be read (and not commanded).
● AO and DO points can be both read and commanded.
● For compatibility with existing APOGEE tools, Points 1, 2, 20, and 29 are the
traditional FLN points ADDRESS, APPLICATION, OVRD TIME, and DAY.NGT.
● When the PXC-16 is using the default application, the 16 physical I/O points (1 to
16) in the PXC Compact on P1 are mapped to the corresponding P1 points 31 to
46.
● When the PXC-24 is using the default application, the 24 physical I/O points (1 to
24) in the PXC Compact on P1 are mapped to the corresponding P1 points 31 to
54.
PXM10S/T Product Overview and Description
NOTE:
All figures show the BACnet version of the PXM10S and PXM10T
. The appearance of
the proprietary version may differ slightly.
PXM10S and PXM10T are optional controller mounted Operator Display modules that
provide a password protected user interface. This interface allows you to interact with
the existing field panel database and its immediate sub-networked Siemens (FLN)
devices. (Optional remote enclosure door mount kit also available.)
NOTE:
All unacknowledged alarms are viewable even if you are not logged into the module.
Product Description
The PXM10S and PXM10T modules are available as an upgrade for use with all
Siemens Compact and Modular Series field panels to provide additional local operator
capabilities. The PXM10S and PXM10T modules are field mounted and replace the
field panel covers.
There are three dedicated buttons, ALARM, INFO, ESC and one push DIAL. These
buttons, the push dial, and LCD display screen allow for interactive feedback at the
field panel controller.
The PXM10S and PXM10T modules support all the languages loaded in the host field
panel.
There are two versions of the modules as follows:
● PXM10S has all available options, including Point Monitor and optional blue
backlight color.
● PXM10T does not include the Point Monitor or the optional blue backlight color.