Installation Instructions

Document No. 553-168
Installation Instructions
November 03, 2017
Siemens Industry, Inc. Page 3 of 4
Figure 1. Front View of the PXC Compact Series (PXC-24 shown).
Option 1: Mounting the Controller on a DIN
Rail
NOTE: To provide a minimum clearance for wiring,
allow 6 inches (15 cm) from the center of the
DIN rail to obstructions on either side.
Installing the DIN Rail
Do the following if the DIN rail is not already installed:
1. Align and level the DIN rail on the mounting surface
or the backplane of the enclosure.
2. Mark the position of the mounting holes at either
end of the DIN rail.
3. Using wall anchors, if necessary, attach the DIN rail
to the surface or the backplane.
NOTE: For longer DIN rails, use one mounting screw
per running foot of DIN rail.
Installing the PXC Compact
1. Slide out the mounting tabs.
2. Align the channel on the back of the device with the
DIN rail.
3. Using a flat-blade screwdriver, push in each
mounting tab until it clips onto the DIN rail.
4. Continue with Completing the Installation.
Option 2: Fastening the Controller with
Screws
NOTE: Allow a minimum clearance of 3 inches (7.6 cm)
around the controller ports and connectors for
terminating wires.
1. Select one of the following options for fastening the
controller:
Drive screws through the four slide-out
mounting tabs.
Drive screws through the two mounting holes in
the controller cover and through two mounting
tabs at the opposite corners (see Figure 1).