Data Sheet for Product

11/18
Siemens PXC….D – Automation stations, compact model CM1N9215en_25
Smart Infrastructure 2022-01-15
PXC12-E.D
1, 2
24 V ~,
Operating voltage
AC 24 V
3 Functional earth CFC IOAddr
4 … 9
DO1, DO2
2 Digital outputs (Relays)
DO1: C=5.1
25 … 30
U1 … U4
4 Analog inputs / outputs
with
Q
250
xx1: C=4.1 *)
31 … 36
U5 … U8
4 Analog inputs / outputs
xx5: C=1.1 *)
58 … 60
DI1, DI2
2 Digital inputs
DI1: C=3.1
61, 62
CP+, CP
PPS2 bus (for up to 5 QAX... room units)
A
Ethernet socket
C
HMI
RJ45 socket for
PXM10
PXC22-E.D
1, 2
24 V ~,
Operating voltage AC 24 V
3 Functional earth CFC IOAddr
4 … 21
DO1 … DO6
6 Digital outputs (Relays)
DO1: C=5.1
25 … 30
U1 …U4
4 Universal inputs / outputs
with
Q
250
xx1: C=4.1 *)
31 … 52
U5
…U16
12 Universal inputs / outputs
xx5: C=1.1 *)
61, 62
CP+, CP
PPS2 bus (for up to 5 QAX... room units)
A
Ethernet socket
C
HMI
RJ45 socket for
PXM10
*) Signal type when no application is loaded (wiring test):
U1…U4: xx = Y10S, U5…U16: xx = R1K
Observe the technical data for the relay outputs.
Local installation regulations must be observed.
58
60
59
61
62
DI1
DI2
U1 U2 U3 U4 U5 U6 U7 U8
U1 U2U3 U4 U5 U6 U7 U8 U9 U10 U11 U12 U13 U14 U15 U16
STOP
Caution!