Data Sheet for Product

2/18
Siemens PXC….D – Automation stations, compact model CM1N9215en_25
Smart Infrastructure 2022-01-15
Functions
Compact, freely programmable automation stations for HVAC and building control
systems.
Management functions (alarm management with alarm routing, schedulers, trend
functions, remote management, access protection with individually defined user
profiles and categories).
For stand-alone applications or for use within a device or system network.
BTL-tested BACnet communications on LonTalk, PTP or IP, compliant with BACnet
standard (Rev. 1.12 -for Desigo V6.0 and later) including B-BC profile.
AMEV profiles AS-A and AS-B to recommendation "BACnet 2011 - Version 1.2
(for Desigo V6.0 and later)"
Freely programmable, using the D-MAP programming language (close resemblance
to CEN standard 11312). All function blocks, available in libraries, can be graphically
connected.
Engineering and commissioning using the Desigo Xworks Plus tool.
Scalable range of touch panels, Web solutions and operator units
Direct connection of field devices; the devices provide power supply for inputs and
outputs as well as for active sensors.
Low voltage protection and start-up management to protect the devices against
fluctuating voltage.
Types
Automation stations
PXC12-E.D
1
)
PXC12.D
2)
PXC22-E.D
1
)
PXC22.D
2)
PXC22.1-E.D
1)
PXC22.1.D
2)
PXC36.1-E.D
1)
PXC36.1.D
2)
Total number of inputs / outputs (Onboard)
12
22
22
36
Number of digital inputs (DI)
2
-
-
4
Number of universal inputs / outputs (UIO)
8
16
16
24
whereof UIO supporting Q250
(DC 0/24 V
(4) (4) (4) (6)
Number of relay outputs (DO)
2
6
6
8
Number TX-I/O data points
3)
16
28
Number of physical data points
3)
(Onboard + TX
-
I/O)
- - 38 64
Number of TX Open modules
-
-
5
5
Number of data points
3)
(Onboard + TX
-
I/O + TX Open)
- - 400 400
1)
Communications BACnet / IP
2)
Communications BACnet / LonTalk
3)
Communications island bus
UIO Universal input and output, suited for the following signal types:
Passive sensor LG-Ni 1000, Ni 1000, Pt 1000, T1
Active sensor DC 0…10 V
Volt-free binary contact for signaling function
Counter up to 20 Hz (C)
Analog output DC 0…10 V
Part of the UIOs can be configured for binary switching with a load of
24
V
/
20mA.
PXC12/22..D: 4 UIOs; PXC36: 6 UIOs
DI
Binary input for signaling function
7 mA, DC 20...25 V
DO
Rela
y output
AC 230 V / 2 A
for binary switching, switchover contact
Input and output