Operating Instructions

Table Of Contents
Chapter 2Hardware Features
TX-I/O Product Range Overview
0
| 118
Siemens Industry, Inc.
Owner's Manual
553-104
Building Technologies
2018-10-01
When replacing the plug-in I/O module, the address key must first be swiveled
outward. This switches the load off but values remain saved in the PXC Modular, PXC-
36, or P1 BIM. The key remains plugged into the terminal base so that the PXC
Modular, PXC-36, or P1 BIM can communicate the required function to the new I/O
module.
Reset Key
The reset key sets the module back to the factory settings (default function on each of
the I/O points):
The reset key is inserted in place of the address key and then swiveled out again.
The module indicates the reset by briefly lighting all its I/O status LEDs.
Note that a reset is only possible when the module is supplied with 24 Vdc.
TX-I/O Power Supply and Bus Modules
The TX-I/O™ Power Supply and Bus Modules provide power, communications, and
expansion options for the TX-I/O Island Bus.
Power and Communication Modules
The TX-I/O Power Supply and Bus Connection Module provide the following functions
for the island bus:
Function
Product
TX-I/O Bus Communication
24 Vdc power
24 Vac power
TX-I/O Power Supply
(TXS1.12F4)
Signal pass-thru
Output 28.8 W
(1.2A at 24 Vdc)
NEC Class 2 Output , 96 VA max.,
fused at 4A
Class 1 Power Limited Input, 150
VA max.
Bus Connection Module
(TXS1.EF4)
Signal pass-thru
Allows for external
connection of I/O signals.
Pass-thru
NEC Class 2 Output, 96 VA max.,
fused at 4A
Class 1 Power Limited Input, 96 VA
max.
NOTE: 10A versions are not sold in North America.
The P1 Bus Interface Module (BIM) provides the following functions for the island bus:
Function
Product
TX-I/O Bus Communication
24 Vdc power
24 Vac power
P1 Bus Interface Module
(TXB1.P1)
Protocol translation
14.4 W (0.6A at
24 Vdc)
NEC Class 2 Output, 96 VA max.,
fused at 4A
Class 1 Power Limited Input, 125
VA max.