Chapter 1—Introduction
APOGEE Automation Networking
26
| 118
Siemens Industry, Inc.
Owner's Manual
553-104
Building Technologies
2018-10-01
BACnet MS/TP Automation Level Network
BACnet field panels communicate over a customer’s Ethernet cabling and IP network
using the ASHRAE Building Automation and Control Networking (BACnet) MS/TP
protocol.
● One Insight workstation can administer up to 64 Ethernet based MS/TP ALNs.
● Up to 10 BACnet MS/TP ALN field panels can reside on an MS/TP network
segment (1000 maximum per Insight workstation). Network segments must be
physically separated.
● BACnet devices (field panels or Insight workstations) can be set up as one of the
following:
– A standard BACnet MS/TP device
– A BACnet Broadcast Management Device (BBMD)
– A foreign device