Operating Instructions
Table Of Contents
- Cyber security disclaimer
- How to Use This Manual
- Chapter 1—Introduction
- Chapter 2—Hardware Features
- 16- and 24-Point Compact Series Diagram
- 36-Point Compact Series Product Diagram
- Supported Point Types
- Compact Series Backup Batteries
- Memory
- Communication Connections
- Compact Series Specifications
- BACnet Compact Series Specifications
- Compact Series Smoke Control Application Requirements
- HOA (Hand-Off-Auto) Upgrade Kits
- PXC Compact on P1
- PXM10S/T Product Overview and Description
- Unitary Equipment Controller
- TX-I/O Product Range Overview
- PX Series Enclosures and Service Boxes
- Chapter 3—Applications
- Chapter 4—Troubleshooting
- Glossary
- Index
Chapter 2—Hardware Features
BACnet Compact Series Specifications
0
48
| 118
Siemens Industry, Inc.
Owner's Manual
553-104
Building Technologies
2018-10-01
Agency Listings
UL
UL864 UUKL Smoke Control Equipment (except UEC and rooftop models)
UL864 UUKL7 Smoke Control Equipment (except UEC and rooftop models)
CAN/ULC-S527-M8 (except rooftop models)
UL916 PAZX (all models)
UL916 PAZX7 (all models)
Agency Compliance
FCC Compliance CFR47 Part 15, Subpart B, Class B
Australian EMC Framework
European EMC Directive (CE)
European Low Voltage Directive (LVD)
RoHS Compliant
OSHPD Seismic Certification
Product meets OSHPD Special Seismic Preapproval certification (OSH-0217-10) under California
Building Code 2010 (CBC2010) and International Building Code 2009 (IBC2009) when installed
within the following Siemens enclosure part numbers: PXA-ENC18, PXA-ENC19, or PXA-ENC34.
BTL BACnet Testing Laboratories (BTL) Certified, Firmware Revision 3.0 and later
Compact Series Smoke Control Application
Requirements
CAUTION
The 115V or 230V PX Series Service Box is required for UL864 and NFPA92A
compliant installations. For more information, see the
PX Series Service Box
Assemblies Installation Instructions
(553-131) or the
Service Box Installation
Instructions
(586-135). For non-UL864 and non-NFPA92A applications, any 24 Vac
Class 2 transformer can be used.
NOTE:
For smoke control applications over BACnet/IP or Ethernet TCP/IP (P2), the field
panel must be connected to the Automation Level Network (ALN) through an Ethernet
switch that is UL Listed for Fire Signaling. ALN and FLN circuits are supervised.
For smoke control applications, mount the PXC Compact inside a 19-inch or 34-inch
PX Series enclosure (PXA-ENC19 or PXA-ENC34). For more information, see the
19"
and 34" PX Series Enclosure Assemblies Installation Instructions
(553-130).
Service Modem Kit (538-915) is required for remote connection to the HMI of a PXC
Compact running smoke control applications. The modem, serial cable, and surge
suppressor must be installed inside the 19-inch or 34-inch PX Series enclosure with a
Service Box.
For modems used with smoke control applications:
Modem Requirements
● The UL864 Listed surge protector (538-600) is required.
● Devices connected between the USB port and the UL Listed surge protector must
be located within the same room.