Installation Instructions

Document No. A5W00125545
Installation Instructions
September 8, 2020
Page 2 of 4 Siemens Industry, Inc.
Earth Grounding of System Neutral
System Neutral (⊥) must be continuous throughout the
TX-I/O bus.
System Neutral is required to be earth-grounded at a
single point only.
Connect 24 Vdc Power Supply common or Diode
Decoupling Module common to the building-approved
earth ground at the terminal block.
Energy Management Applications
Open Energy Management devices must be mounted in
one or more NEMA Type 1 or better enclosures for both
primary and secondary panels.
Required Tools and Materials
Wire stripper/side cutter
Small 9/64-inch flat-blade screwdriver
Digital multimeter (DMM)
Phillips #2 (3.5mm) screwdrive
Expected Installation Time
20 minutes
Prerequisites
CAUTION
No power wiring is connected to
the PXC Modular or other TX-I/O
components at this time.
General Installation Requirements are met
Earth Grounding of System Neutral
Energy Management Applications
Mounting in NEMA Type 1 enclosures (primary and
secondary panels):
Enclosure(s) installed including DIN rail
The power source(s) installed, as needed
The power sources(s) OFF
Panel Power requirements are met
Power cable of correct gauge is available
All necessary power and communication wiring pulled
and terminated per the layout drawing
On the removable plugs provided with the devices
For TX-I/O Modules:
Point wiring is terminated on the TX-I/O Terminal
Base
TX-I/O Modules are either removed from or
parked in the terminal bases
TX-I/O Address Keys are available for each
Module
TX-I/O Module labels have been printed from
System Profile
See the APOGEE
Wiring Guidelines for Field Panels and
Equipment Controllers
(125-3002) for detailed information
TX-I/O Module point wiring diagrams.
Panel Power Requirements
One or more of following power sources are pulled to
each primary and each optional secondary panel:
Required VIN A for Power Supply Unit PSU-A.
1 or 3 phase AC or DC terminated on PSU-A.
Observe Input Voltage Rating and Fusing.
24 Vdc Current rated 10A for small panels.
24 Vdc Current rated 20A for large panels.
Optional Redundant VIN B for PSU-B.
1 or 3 phase AC or DC terminated PSU-B.
Observe Input Voltage Rating and Fusing.
PSU-B must have same Output Voltage and
Current Rating as PSU-A within a panel.
Terminate PSU-A and PSU-B on Diode
Decoupling Module rated same as PSU.
12 AWG wire for 20A DC system supporting PXC100-
E36-DC distributed by four TXS1.EF4.
14 AWG wire for 10A DC system supporting PXC100-
E36-DC distributed by two TXS1.EF4.
18 AWG wire from terminal block to device plug.
Installation
WARNING
Turn OFF AC power at the ON/OFF switch
in the Service Box or transformer
enclosure.