Data Sheet for Product

PXC Modular Series
Ordering Information
6
Siemens Industry, Inc. 149-478
Smart Infrastructure 2020-05-20
Agency Listings
UL
UL 864 UUKL Smoke Control Equipment - Conforms to UL864 9th and 10th Edition.
UL 864 UUKL7 Smoke Control Equipment - Conforms to UL864 9th and 10th Edition.
CAN/ULC-S527-M8
UL 916 PAZX - Conforms to UL916 9th and 10th Edition.
UL 916 PAZX7 - Conforms to UL916 9th and 10th Edition.
Agency Compliance
CFR47 Part 15, Class A; CFR47 Part 15, Class B - with metal enclosure, maximum opening
Australian EMC Framework - with metal enclosure, maximum opening size is 34"
European EMC Directive (CE) - with metal enclosure, maximum opening size is 34"
RoHS Compliant
OSHPD Seismic Certification
Product meets OSHPD Special Seismic Preapproval certification (OSH-0217-10
)
under California
Building Code 2010 (CBC2010) and International Building Code
2009 (IBC2009) when installed
within the following Siemens enclosure part numbers: PXA-ENC18, PXA-ENC19, or PXA-ENC34.
Electrical Disturbance Testing
Dips and Interrupts
per EN 61000-4-11
Electrical Fast Transients (EPT)
per EN 61000-4-4, 1 kV signal, 2 kV AC power
Electrical Surge Immunity
per EN 61000-4-5
AC power: 2 kV common mode, 1 kV differential mode
Signal lines: 1 kV CM, 5 kV DM
Electrostatic Discharge (ESD)
per EN 61000-4-2, 4 kV contact, 8 kV air discharge
RF Conducted Immunity
per EN 61000-4-6 @ 10V
RF Radiated Immunity
per EN 61000-4-3 @ 10V/m
Ordering Information
PXC Modular Series
Product Number
Description
PXC00-PE96.A PXC Modular, Ethernet/IP or RS-485 ALN, P1 FLN. PXX-485.3 is also required as the connection to the
FLN devices.
PXC100-PE96.A PXC Modular, Ethernet/IP or RS-485 ALN, P1 FLN, self-forming TX-I/O Island Bus. PXX-485.3 is also
required as the connection to the FLN devices.
PXX-485.3 Provides FLN support for the PXC Modular. Includes three RS-485 P1 FLN connections or one MS/TP
FLN connection; maximum of 96 devices supported.
Optional Licenses
Product Number
Description
PXF-TXIO.A License to enable the Island Bus on PXC00-E96.A and PXC00-PE96.A.
LSM-VAEM License to enable Virtual AEM support when the P2 ALN is connected to RS-485
LSM-ADAPT
License to use the Adaptive Control added in FW 2.8.18 and later