Operating Environment
Ambient operating environment
Operate in a dry location, which is protected from exposure to salt spray or other
corrosive elements. Exposure to flammable or explosive vapors must be prevented.
Shipping and storage environment -13°F to 158°F (-25°C to 70°C)
Relative Humidity 5% to 95% rh, non-condensing
Mounting Surface
Building wall or structural member (Do not mount on HVAC components or any
other vibrating surface.)
CE Compliance
Requires installation inside a metal enclosure rated at IP30 minimum.
Smoke Control Applications
Requires installation inside a PX series enclosure
Vibration Compliance to IEC 60721, 3M2, and 2M2
Protection to EN60529 IP 20
Agency Listings
UL
UL 864 UUKL Smoke Control Equipment - Conforms to UL864 9th and 10th Edition.
UL 864 UUKL7 Smoke Control Equipment - Conforms to UL864 9th and 10th Edition.
CAN/ULC-S527-M8
UL 916 PAZX - Conforms to UL916 9th and 10th Edition.
UL 916 PAZX7 - Conforms to UL916 9th and 10th Edition.
Agency Compliance CFR47 Part 15, Class A; CFR47 Part 15, Class B - with metal enclosure, maximum
opening
Australian EMC Framework - with metal enclosure, maximum opening size is 34"
European EMC Directive (CE) - with metal enclosure, maximum opening size is 34"
RoHS Compliant
OSHPD Seismic Certification Product meets OSHPD Special Seismic Preapproval certification (OSH-0217-10)
under
California Building Code 2010 (CBC2010) and International Building Code 2009 (IBC2009)
when installed within the following Siemens enclosure part numbers: PXA-ENC18, PXA-
ENC19, or PXA-ENC34.
BTL BACnet Testing Laboratories (BTL) Certified, Firmware Revision 3.0 and later
Electrical Disturbance Testing
Dips and Interrupts
per EN 61000-4-11
Electrical Fast Transients (EPT)
per EN 61000-4-4, 1 kV signal, 2 kV AC power
Electrical Surge Immunity
per EN 61000-4-5
AC power: 2 kV common mode, 1 kV differential mode
Signal lines: 1 kV CM, 5 kV DM
Electrostatic Discharge (ESD)
per EN 61000-4-2, 4 kV contact, 8 kV air discharge
RF Conducted Immunity
per EN 61000-4-6 @ 10V
RF Radiated Immunity