Siemens PXC-NRUF Automation station, compact series CM2N9760en_07
Building Technologies 2015-12-23
RUN
STATUS
SERVICE
TX
INFO
9762z10
LOW BATT
LED
Color
Activity
Function
RUN Green Continuously off
Continuously on
No supply present.
Supply present (LED controlled by SW).
STATUS
Red
Continuously off
Continuously on
Flashes quickly
Normal condition
Hardware error recognized during self test
or automation station in a state of "coma".
There is no valid firmware present.
SERVICE Red Continuously off
Flashing
Flashes in wink
command rhythm *
Continuously on
L
ONWORKS node is configured.
L
ONWORKS node is not configured.
Physical identification of the automation
upon receipt of the wink command.
Neuron chip faulty or service button is
pushed in.
TX
Yellow
Flashing
Data traffic on LONWORKS bus.
LOW
BATT
Red Continuously off
Continuously on
Batteries OK (LED controlled by SW).
Replace one or both batteries.
INFO
Red
Freely programmable.
*
Wink command rhythm:
2s
1s
21s
5 Hz 5 Hz
00408
2s
1s
Identification of the automation station on the L
ONWORKS network:
refer to "commissioning".
Disposal
The device is classified as waste electronic equipment in terms of the European
Directive 2012/19/EU (WEEE) and should not be disposed of as unsorted
municipal waste.
The relevant national legal rules are to be adhered to.
Regarding disposal, use the systems setup for collecting electronic waste.
Observe all local and applicable laws.
Mounting notes
The device can be attached directly to any surface with four screws, e.g. on the
panel's base plate.
Plug-in screw terminal blocks are provided to connect field devices, power and bus
wiring. The other interfaces are connected using the quick plug-in connections.
Do not open the device. All service functions are accessible via the lid.
LED displays
Service button