User Manual

3 / 16
Siemens PXC-NRUF Automation station, compact series CM2N9760en_07
Building Technologies 2015-12-23
Equipment combinations
Various options exist to operating automation stations PXC-NRUF:
Room device QAX... on the PPS2 interface. Up to a maximum of five room
devices QAX... (without QAX5...) can be connected. Details on PPS2
communication are described in the Desigo Technical principles manual
(Section "I/O blocks", subsection "PPS2 addressing").
Local operator unit PXM10 *), is connected with cable PXA-C1.
Operator unit PXM20 *), is connecting with cable PXA-C1, for local operation or
for decentralized operation of an entire plant connected within a BACnet /
LonTalk network.
*) Only one operator unit can be connected (PXM10 or PXM 20).
The following web controllers support remote monitoring and operation using a
standard Internet browser:
PXC...-E.D with PXA40-W1 or PXA40-W2.
Technical design
Universal inputs (UI 1 ... 16)can be used for active sensor elements as well as
potential-free contracts for signaling functions.
Digital inputs (DI 18) allow non-potential-free reporting functions.
They are electrically isolated from the system and from one another.
Digital inputs (DI 916) allow reporting functions (potential-free).
Digital inputs (DI 1724) allow reporting and counting functions (potential-free).
Universal outputs (UO 18) can, on the one hand, control modulating
actuators, on the other hand, they can be programmed for binary switching
functions via the program structure.
Relay outputs (DO 116) are designed for switching functions up to a maximum
of AC/DC 42 V, 2 A.
Operation
Note
Web operation
Inputs
Outputs