User Manual

2 / 10
Siemens PXC001 System controllers CM1N9223en_09
Smart Infrastructure 2020-05-30
Use
The system controllers support the integration of Desigo RXB/RXL room
controllers as well as third-party devices and systems via KNX, Modbus or M-
Bus etc. in the automation level using BACnet/LonTalk or BACnet/IP
Mapping and monitoring of third-party disciplines as HVAC, light, PLC etc.
Functionality as freely programmable system controllers for standard or
proprietary protocol applications
Functions
The system controllers provide the infrastructure to hold and execute the system
and application specific functions. They are freely programmable.
Comprehensive management and system functions are available:
Alarm management
Time scheduling
Trends
Access protection
Type summary
Type
PXC001.D
PXC001-E.D
Type
PXA40-RS1
PXA40-RS2
Equipment combinations
PXC001.D
PXC001-E.D
PXA40-RS1
PXA40-RS2
Interfaces
KNX
X
--
--
Serial RS232
X
--
--
Serial RS485
X
--
--
Network functions
Integration KNX
2000 DP
--
--
Integration M-Bus
250 DP
800 DP
2000 DP
Integration Modbus
250 DP
800 DP
2000 DP
Integration SCL
250 DP
800 DP
1000 DP
PXA40-… option modules can be plugged and unplugged when the automation
station is operating.
The functionality is available immediately after inserting.
The functionality disappears approx.1 minute after unplugging.
Option modules are
"hot-pluggable"