User Manual

Planning (hardware)
Ethernet
7
A6V11666339_en--_b 25 | 35
7.5 Ethernet
For detailed information on Ethernet, see:
Ethernet, TCP/IP, MS/TP and BACnet fundamentals
(CM110666)
Practical guide on IP networks in building automation and control
(CM110668)
Practical guide on BACnet networks in building automation and control
(A6V11159798)
Desigo building automation and control - Technical principles
(CM110664)
IT security on installations with Desigo
(CM110663)
The following provides only specific notes on topology.
Topologies
You can use the following bus topologies:
Star topology
Line topology (for web server)
Star topology
Touch panels can only be connected in a star topology.
Line topology
The number of devices is limited to 20 for a line topology (daisy chain).
Availability/reliability
The Ethernet switch does not work on a device without 24 V power. The following devices, connected in a line
topology, are no longer on the network. As a result, each web server should be separately powered with 24 V
for secure system operation.
Switch
Switch Switch
Switch
PXG3.Wx00
PXG3.Wx00
PXG3.Wx00PXG3.Wx00
Segment (S)
Switch
Switch Switch
Switch
PXG3.Wx00
PXG3.Wx00
PXG3.Wx00PXG3.Wx00
Segment (S)
Segment (S)
Switch