User Manual

System limits
LonWorks limits
6
A6V11170804_en--_l 21 | 41
6.5 LonWorks limits
Use the router PXG3.L / PXG3.M with HW Index C only.
Data point integration: LonWorks devices take a lot longer than IP devices due to the lower network speed.
Reference value: Approximately 30 times longer (depending on the project setup).
To avoid timeout problems,
Use the workflow: Data point integration.
Integrate at the standard user level
Avoid the "Cache" dialog
Create templates for individual data point selection for LonWorks devices on IP devices.
These templates can then be imported to the LonWorks devices.
6.6 Limits for MS/TP
Use the router PXG3.L / PXG3.M with HW Index C only.
Data point integration: MS/TP devices are considerably slower than IP devices due to the lower network speed.
Reference value: Approximately 15 times slower (depending on the project setup).
MS/TP is tested with 10 devices that support COV (e.g. DXR2). Recommendation: Assign or integrate a
maximum of 10 MS/TP devices on one network branch. More devices and/or network complexity are permitted,
but they may result in longer and inconsistent times and degraded performance.
Assign devices offline/online:
More than 10 devices degrade performance in ABT-SSA.
Additional network branches degrade performance in ABT-SSA.
Device learning offline/online:
More than 10 devices takes longer.
The times are slower with additional network branches.
Device restart (e.g., after the power returns):
More than 10 devices takes longer.
The times are slower for a restart.
The following limits and constraints must be considered if the MS/TP devices do not support COV, i.e. only
polling:
Disable the list view core function (user profile setting in ABT Site)
Limit to one concurrent operating client (limit your network topology)
Set baud rate to 38400 or higher
Only use the online trends functionality very limited
Limit the points per graphic to 15
6.7 Supported BACnet objects
The BACnet objects supported in Desigo Control Point are listed in the Appendix [ 40].