6.3 Graphics-based operation
Data point capacity is limited for graphical operation (data point integration).
The figures below apply to integration over the standard user level and where full graphical operation of all data
points is required.
Desigo primary plant Desigo room automation
Access level for integration Extended operation Standard operation
Max. number * Number of hardware-I/Os ** Number of simple rooms
(HVAC only)
Number of complex rooms
(HVAC, lighting, shading)
PXG3.W100-1
400 30 10
PXG3.W200-1
800 60 20
PXM30.E
200 15 5
PXM40.E
400 30 10
PXM50.E
400 30 10
PXM30-1, PXM40-1, PXM50-1
n.a. (see limits for PXG3.Wx00-1)
* The selection of integrated data points can be optimized and individually customized with the Advanced Tool in the data point
integration function.
** Primary plants: Per hardware I/O some 2.5 BACnet objects are integrated on average.