User Manual
System limits
Limits for MS/TP
5
18 | 35 A6V11666339_en--_d
5.4 Limits for MS/TP
Use the router PXG3.L / PXG3.M with HW Index C only.
Data point integration: MS/TP devices are considerably slower than IP devices due to the lower network speed.
Reference value: Approximately 15 times slower (depending on the project setup).
MS/TP is tested with 10 devices that support COV (e.g. DXR2). Recommendation: Assign or integrate a
maximum of 10 MS/TP devices on one network branch. More devices and/or network complexity are permitted,
but they may result in longer and inconsistent times and degraded performance.
● Assign devices offline/online:
More than 10 devices degrade performance in ABT-SSA.
Additional network branches degrade performance in ABT-SSA.
● Device learning offline/online:
More than 10 devices takes longer.
The times are slower with additional network branches.
● Device restart (e.g., after the power returns):
More than 10 devices takes longer.
The times are slower for a restart.
The following limits and constraints must be considered if the MS/TP devices do not support COV, i.e. only
polling:
● Disable the list view core function (user profile setting in ABT Site)
● Limit to one concurrent operating client (limit your network topology)
● Set baud rate to 38400 or higher
● Only use the online trends functionality very limited
● Limit the points per graphic to 15
5.5 Supported BACnet objects
The BACnet objects supported in Desigo Control Point are listed in the Appendix.
5.6 BACnet revision
System compatibility PXM50-1
PXM40-1
PXM30-1
PXM50.E
PXM40.E
PXM30.E
PXG3.W100-1 PXG3.W200-1
BACnet devices
n.a. as of BACnet revision 1.05